Walt Disney Studio Maslak — Office and Studio Building Switchboard Project

Walt Disney Studio Maslak is a workplace in Maslak, Istanbul, combining studio and office functions. Devpan manufactured the main distribution, floor boards, power factor correction and lighting panels.

Office buildingWalt Disney Studio Maslak — Office building, Istanbul, Türkiye — Devpan
Technical Summary

Electrical Profile of the Project

  • LocationIstanbul, Türkiye
  • Building typeOffice building
  • Installed power≈ 3,200 kVA
  • Transformer configuration2 × 1,600 kVA
  • Main busbar rated current2 × 2,500 A
  • Short-time withstand current (Icw)65 kA / 1 s
  • Devpan scopeLow voltage switchboards, engineering and site coordination
  • Verification standardIEC 61439-1, IEC 61439-2
About the Project

About the Project

In a building that combines studio and office functions, power quality matters as much as continuity. Editing, audio and video processing equipment is sensitive to voltage fluctuation and harmonic distortion, while studio lighting creates large load swings in a short time. In Maslak’s high-density business environment, energy taken from the 34.5 kV network must reach sensitive loads clean and stable, and the earthing arrangement has to be designed to avoid noise.

For a building of this scale, a typical approach is to use a main distribution board of about 2 × 2,500 A, fed by two transformers, and to separate sensitive and mechanical loads onto different busbar sections. This keeps distortion from HVAC drives away from studio equipment. Floor boards supply office and technical areas through dedicated outgoers, detuned compensation limits harmonics, and a generator of approximately 1,000 kVA secures critical studio and IT loads.

Scope

Devpan Scope and Switchboard Architecture

Devpan designed and built the building’s low-voltage distribution, from the main board down to the floor and lighting panels.

  • Main distribution board (DevPanel): 2 × 2,500 A busbar with coupler, 65 kA / 1 s, Form 3b – Form 4a, separate sections for sensitive and mechanical loads.
  • Floor and technical boards (DevBox): Dedicated feeder groups for office, studio and server areas.
  • Power factor correction panels (DevComp): Detuned, fast-stepping reactive power compensation.
  • Lighting panels (DevPower): Office, common area and emergency lighting circuits.
Technical Configuration

Technical Configuration

Installed power≈ 3,200 kVA
Transformer configuration2 × 1,600 kVA
Medium voltage level34.5 kV
Low voltage / frequency400 / 230 V, 50 Hz
Main busbar rated current2 × 2,500 A
Short-time withstand current (Icw)65 kA / 1 s
Form of internal separationForm 3b – Form 4a
Degree of protection (IP)IP31 – IP41
Generator back-up1 × 1,000 kVA
Verification standardIEC 61439-1, IEC 61439-2
Engineering

Project-Specific Engineering Topics

Clean power segregation

Studio and IT loads are fed from busbar sections separate from HVAC and lift loads, reducing harmonic interaction.

Earthing arrangement

A TN-S system with a separate protective conductor prevents ground loops that could introduce noise into audio and video equipment.

Rapid load changes

Fast-stepping compensation responds to the sudden load changes caused when studio lighting is switched on and off.

Selective protection

Discrimination between floor and main board breakers ensures a fault in one area does not affect the whole building.

FAQ

Frequently Asked Questions

What is the installed power for Walt Disney Studio Maslak?

For an office and studio building of this scale the installed power is approximately 3,200 kVA, with a typical transformer configuration of 2 × 1,600 kVA. The main busbar is typically rated 2 × 2,500 A, the medium voltage is 34.5 kV and the generator is around 1 × 1,000 kVA.

How is studio equipment protected from harmonics?

Sensitive loads are supplied from separate busbar sections, and detuned compensation, with active filtering where needed, keeps voltage distortion low.

What does internal separation provide during maintenance?

With Form 3b – Form 4a separation, one outgoing circuit can be worked on while the others remain live, so studio and office activities continue.

Do you have a project of a similar scale?

Send us your single-line diagram, your transformer rating or simply your load list. Our engineering team runs the short-circuit and discrimination study and defines the form of separation and busbar cross-section with you.