The C/k setting is the threshold that determines how precisely a reactive power control relay switches capacitor steps in and out. In short, it is the current of the smallest compensation step as reflected on the current transformer secondary. If it is set incorrectly, the bank either hunts continuously or the facility remains under-compensated and incurs reactive energy penalties.
The Current Transformer and C/k
A current transformer converts the high current flowing through the main line into a measurable secondary current (usually 5 A or 1 A). The reactive power control relay sees the facility’s reactive demand through this secondary current. The relay compares the change it measures in the reactive component with the change the smallest step would cause; this comparison threshold is the C/k value. If the threshold is chosen correctly, the relay switches steps only when a truly significant reactive difference occurs.
C/k Calculation Formula
The C/k value is found by dividing the current drawn by the smallest step by the current transformer ratio. The formula is:
Worked example: If the smallest step in the capacitor bank is 12.5 kVAr, the supply voltage is 400 V and the current transformer is 400/5, then k = 80. Hence C/k = (12.5 × 1000) ÷ (1.732 × 400 × 80) = 12,500 ÷ 55,424 ≈ 0.23, and this value is entered into the relay.
Ready-Made C/k Table for 400 V
The table below gives C/k values calculated for a 400 V network according to the smallest step rating and the current transformer ratio. Cells highlighted in blue fall within the 0.10 – 1.00 range in which relays operate reliably.
| Smallest step (kVAr) | 100/5 | 200/5 | 300/5 | 400/5 | 600/5 | 800/5 | 1000/5 | 1500/5 | 2000/5 |
|---|---|---|---|---|---|---|---|---|---|
| 5 | 0.36 | 0.18 | 0.12 | 0.09 | 0.06 | 0.05 | 0.04 | 0.02 | 0.02 |
| 7.5 | 0.54 | 0.27 | 0.18 | 0.14 | 0.09 | 0.07 | 0.05 | 0.04 | 0.03 |
| 10 | 0.72 | 0.36 | 0.24 | 0.18 | 0.12 | 0.09 | 0.07 | 0.05 | 0.04 |
| 12.5 | 0.90 | 0.45 | 0.30 | 0.23 | 0.15 | 0.11 | 0.09 | 0.06 | 0.05 |
| 15 | 1.08 | 0.54 | 0.36 | 0.27 | 0.18 | 0.14 | 0.11 | 0.07 | 0.05 |
| 20 | 1.44 | 0.72 | 0.48 | 0.36 | 0.24 | 0.18 | 0.14 | 0.10 | 0.07 |
| 25 | 1.80 | 0.90 | 0.60 | 0.45 | 0.30 | 0.23 | 0.18 | 0.12 | 0.09 |
| 30 | 2.17 | 1.08 | 0.72 | 0.54 | 0.36 | 0.27 | 0.22 | 0.14 | 0.11 |
| 50 | 3.61 | 1.80 | 1.20 | 0.90 | 0.60 | 0.45 | 0.36 | 0.24 | 0.18 |
A value below 0.10 indicates that the current transformer is oversized, while a value above 1.00 indicates that the smallest step is too large. In either case, the compensation design should be reviewed.
C/k Setting Step by Step
- Identify the smallest step. Note the rating of the smallest capacitor group in the bank in kVAr.
- Read the current transformer ratio. Divide the primary current on the nameplate by the secondary current to find k.
- Apply the formula. Calculate the C/k value or read it from the table above.
- Check the connection. Make sure the current transformer sees the entire facility load and that the P1-P2 direction and S1-S2 terminals are correct.
- Enter the value into the relay. Enter the calculated value in the relay’s C/k parameter; if the relay has automatic learning, compare its result with your calculation.
- Observe the behavior. Check that steps switch in and out without hunting and that the power factor stays at the target value.

A correct C/k value only means something with correct installation.
The current transformer is fitted on the main conductor with the P1-P2 direction toward the load; the secondary leads are taken from terminals S1 and S2 to the relay’s measuring circuit.Leaving the secondary circuit open under load causes dangerously high voltage in the current transformer. That is why the secondary terminals are short-circuited before any work on the measuring circuit.The transformer ratio is read from the nameplate and recorded; the C/k calculation is based on this ratio and the rating of the compensation step.Secondary wiring is kept short and direct; if the measuring circuit must share a duct with power cables, a gap is left between them, otherwise interference will affect the measurement.
Common Mistakes
- Installing the current transformer at a point where it does not see the current of the compensation bank.
- Connecting P1-P2 in reverse, so that the relay interprets the load as generation.
- Leaving the current transformer secondary open under load, which produces dangerously high voltage.
- Failing to update the C/k value after step ratings have been changed.
- Calculating k with a 5 A assumption for transformers with a 1 A secondary.
- Using capacitors without reactors in facilities with high harmonic loads, which distorts the measurement.
Is your power factor correction panel working properly?
An incorrect C/k setting shortens contactor and capacitor life and increases the risk of reactive energy penalties. Devpan verifies the current transformer selection, step plan and relay parameters of your power factor correction panels together with on-site measurements.Contact us for compensation support
- Formula: C/k = (Q × 1000) / (√3 × U × k)
- Q: Rating of the smallest capacitor step (kVAr)
- U: Line-to-line supply voltage (usually 400 V)
- k: Current transformer ratio (e.g. k = 80 for 400/5)
- Typical range: values between 0.10 and 1.00 A are the healthy operating range
- Example: 12.5 kVAr step, 400 V, 400/5 current transformer → C/k ≈ 0.23
Frequently Asked Questions About Current Transformer C/k Setting
What is the C/k setting?
How is the C/k value calculated?
How do I find the current transformer ratio k?
What happens if C/k is set too low?
What happens if C/k is set too high?
Where should the current transformer be installed?
Why are the P1-P2 direction and S1-S2 connection important?
Why must a current transformer secondary never be left open?
Can modern relays set C/k automatically?
Related Technical Information
- Copper Busbar Current-Carrying Capacities – copper busbar tables and correction factors
- Cable Current-Carrying Capacities – YVV (NYY) TS 212 current tables
- Forms of Separation – IEC 61439 form types
- IP Protection Rating – enclosure degrees of protection
- DevComp – reactive power compensation panels
- Automation & SCADA – energy monitoring and metering solutions