What Is Selectivity? Protection Coordination in Switchgear

Selectivity and protection coordination cascade diagram

What Is Selectivity? Protection Coordination in Switchgear

Selectivity means that during a fault only the protective device closest to it opens, while the devices upstream stay closed. Well-built coordination prevents a short circuit on a single motor outgoing from blacking out an entire plant.

Why coordination matters

If a faulty socket in a factory trips the incomer, the problem is not the devices but the coordination. The loss is not only stopped production; restart time, cold inrush currents and process damage add to the cost. That is why coordination belongs at the very beginning of panel design.

Types of selectivity

Coordination can be achieved through three mechanisms, and most installations use them together.

TypePrincipleLimitation
Current selectivityA sufficient margin is left between downstream and upstream trip thresholdsBreaks down if the fault current falls between the two thresholds
Time selectivityA short delay (e.g. 100–300 ms) is set upstreamThe system carries fault current throughout the delay
Energy selectivityThe downstream device limits current so the upstream one does not tripMust be verified against manufacturer tables
Typical protection levelsIncomer — ACB 2000 A, short-time delayedDistribution breaker — MCCB 630 AMotor/outgoing breaker — MCCB 160 AFinal circuit — MCB 32 Adevpan.com
Each level is set to operate later than the one below it.

Total and partial selectivity

Total selectivity means coordination holds up to the highest prospective short-circuit current. Partial selectivity applies only up to a stated current; above that value both devices open together. The technical file should state the limit up to which the assembly is selective. See short-circuit withstand for how these values are established.

What is zone selective interlocking (ZSI)?

The main drawback of time selectivity is that fault current persists during the upstream delay. With ZSI a communication link runs between breakers: when the downstream device sees the fault it sends a restraint signal upstream and holds it back. If no signal arrives, the upstream device trips without delay. Both selectivity and a short clearing time are therefore obtained together.

Do not confuse it with cascading

Cascading, or back-up protection, means that above the downstream device’s own breaking capacity the upstream device assists it. It is economical but not selective: both devices may open during a fault. Selectivity and cascading can deliberately coexist at different levels of the same assembly.

Practical rules in panel design

For coordination to hold in the field, the design should observe the following:

  • Aim for at least a 1:2.5 rated current ratio between consecutive devices
  • Prefer an electronically protected device with short-time settings (Isd/tsd) upstream
  • Use the manufacturer’s selectivity tables rather than assumptions
  • Use selective (type S) RCDs where residual current protection is graded
  • Record the settings on the panel label and in the technical file

Documentation of settings is covered in the panel technical file.

Key takeaways: selectivity

  • Why coordination matters — If a faulty socket in a factory trips the incomer, the problem is not the devices but the coordination.
  • Types of selectivity — Coordination can be achieved through three mechanisms, and most installations use them together.
  • Total and partial selectivity — Total selectivity means coordination holds up to the highest prospective short-circuit current.
  • What is zone selective interlocking (ZSI) — The main drawback of time selectivity is that fault current persists during the upstream delay.
  • Standard source — IEC publication catalogue: iec.ch.

Frequently asked questions

Can thermal-magnetic breakers give total selectivity?

Usually not. Because their magnetic thresholds are fixed, coordination breaks down at high short-circuit currents. Using an electronically protected device at the main level gives far more reliable results.

Is selectivity calculated in software?

Manufacturers’ coordination software and selectivity tables are used. Plotting curves alone is not enough; energy selectivity can only be verified from tables.

Does adding a delay affect short-circuit withstand?

Yes. When the upstream device is delayed, the assembly and its busbars must carry the fault current for that time, so the Icw rating has to be chosen accordingly.

Related articles

Devpan plans protection coordination together with device selection and documents the settings in the technical file. Share your single-line diagram and we will review the coordination with you.