Immanuel Kant Campus — University Campus Switchboard Project

The Immanuel Kant Campus in Kaliningrad is a university campus bringing together lecture halls, laboratories, residences and social buildings. Devpan supplied the main distribution, building distribution, power factor correction and lighting panels.

University campusImmanuel Kant Campus — University campus, Kaliningrad, Russia — Devpan
Technical Summary

Electrical Profile of the Project

  • LocationKaliningrad, Russia
  • Building typeUniversity campus
  • Installed power≈ 6,400 kVA
  • Transformer configuration4 × 1,600 kVA
  • Main busbar rated current2 × 3,200 A
  • Short-time withstand current (Icw)65 kA / 1 s
  • Devpan scopeLow voltage switchboards, engineering and site coordination
  • Verification standardIEC 61439-1, IEC 61439-2
About the Project

About the Project

On a university campus, power is distributed across many buildings with very different usage profiles: lecture halls busy during the day, laboratories drawing steady load around the clock, residences used in the evenings and at night, plus sports and social facilities. Kaliningrad’s damp, cool Baltic climate increases the risk of condensation in plant rooms and extends the heating season. For a campus of this scale the installed power is typically around 6,400 kVA. The distribution system must share load evenly between buildings and prevent a fault in one building from affecting the others.

In the typical solution, four 1,600 kVA transformers fed from the 10 kV distribution connect to a 2 × 3,200 A main board split by a bus coupler, and each building is supplied radially from it. Every building has its own distribution board, and selective protection confines a fault to the affected building or floor. A 2 × 1,250 kVA generator capacity backs up critical laboratory equipment, life-safety systems and emergency lighting. Form 4a – Form 4b construction and IP31 – IP41 enclosures support safe, long-life operation in a humid environment.

Scope

Devpan Scope and Switchboard Architecture

Devpan’s scope covers the low-voltage system from the campus main distribution to building and floor boards.

  • Main distribution boards (DevPanel): 2 × 3,200 A, 65 kA / 1 s, dual section with bus coupler and building feeders.
  • Building and floor boards (DevBox): Sub-distribution for teaching, laboratory, residential and administrative buildings.
  • Power factor correction (DevComp): Automatic stepped compensation that follows the varying campus load.
  • Lighting and power panels (DevPower): Auditorium, corridor, outdoor and emergency lighting circuits.
Technical Configuration

Technical Configuration

Installed power≈ 6,400 kVA
Transformer configuration4 × 1,600 kVA
Medium voltage level10 kV
Low voltage / frequency400 / 230 V, 50 Hz
Main busbar rated current2 × 3,200 A
Short-time withstand current (Icw)65 kA / 1 s
Form of internal separationForm 4a – Form 4b
Degree of protection (IP)IP31 – IP41
Generator back-up2 × 1,250 kVA
Verification standardIEC 61439-1, IEC 61439-2
Engineering

Project-Specific Engineering Topics

Radial multi-building distribution

Each building has its own feeder from the main board, so maintenance or a fault affects only that building.

Diverse usage profiles

Lecture, residence and laboratory loads peak at different times, allowing transformer capacity to be used more efficiently.

Humidity and condensation

Anti-condensation heaters and suitable IP ratings prevent moisture problems, especially in basement plant rooms.

Laboratory supplies

Laboratory equipment that must run continuously is fed from separate, generator-backed circuits.

FAQ

Frequently Asked Questions

What is the installed power for a campus like Immanuel Kant Campus?

For a university campus of this scale the installed power is approximately 6,400 kVA, with a typical transformer configuration of 4 × 1,600 kVA. The main busbar is typically 2 × 3,200 A with a 65 kA / 1 s rating, supplied at 10 kV medium voltage.

How is selectivity achieved between campus buildings?

Building feeder breakers in the main board and protective devices in each building board are coordinated in time and current, so a fault opens only the breaker nearest to it.

How are switchboards protected in a humid climate?

Suitable IP ratings, thermostatically controlled panel heaters and ventilated plant rooms limit the effect of condensation on insulation and contacts.

Do you have a project of a similar scale?

Send us your single-line diagram, your transformer rating or simply your load list. Our engineering team runs the short-circuit and discrimination study and defines the form of separation and busbar cross-section with you.

Request a quotation