Yamanevler Avrupa Konutları — Residential Switchboard Application

İstanbul Yamanevler Avrupa Konutları is a high-density residential project close to a public transport corridor. On this project Devpan produced the main distribution boards, the block metering panels and the motor circuits feeding the lift and car park groups.

Residential complexİstanbul Yamanevler Avrupa Konutları — Residential complex, Istanbul, Türkiye — Devpan
Technical Summary

Electrical Profile of the Project

  • LocationIstanbul, Türkiye
  • Building typeResidential complex
  • Installed power≈ 4,800 kVA
  • Transformer configuration3 × 1,600 kVA
  • Main busbar rated current2 × 2,500 A
  • Short-time withstand current (Icw)65 kA / 1 s
  • Devpan scopeLow voltage switchboards, engineering and site coordination
  • Verification standardIEC 61439-1, IEC 61439-2
About the Project

About the Project

In dense residential projects the lift groups account for only a small share of the total installed power, yet they shape the distribution design noticeably. Starting currents are sudden and repetitive; variable frequency drives generate harmonics, and regenerative drives can feed energy back into the network.

At Yamanevler Avrupa Konutları the lift supply circuits are protected separately, and breaker tripping curves are selected so that starting current is not interpreted as a fault. On the car park side the jet fan groups and the lighting are collected on a separate branch. Compensation is built with detuned reactors against the harmonics produced by the lift drives, which prevents the capacitor stages entering resonance.

Scope

Devpan Scope and Switchboard Architecture

The Devpan scope reaches from main distribution to the block metering panels and the motor supply circuits.

  • Main distribution boards (DevPanel): 2,500 A class, 65 kA / 1 s, main distribution with bus coupler arrangement.
  • Block sub-distribution and metering panels (DevBox): Consumer metering and floor distribution.
  • Lift and booster pump supply circuits: Separately protected outgoing ways with protection settings that allow for starting current.
  • Car park panels (DevPower): Jet fan supply, lighting and fire scenario segregation.
  • Power factor correction (DevComp): Automatic stepped compensation with 7% detuned reactors.
Technical Configuration

Technical Configuration

Installed power≈ 4,800 kVA
Transformer configuration3 × 1,600 kVA
Medium voltage level34.5 kV
Low voltage / frequency400 / 230 V, 50 Hz
Main busbar rated current2 × 2,500 A
Short-time withstand current (Icw)65 kA / 1 s
Form of internal separationForm 3b – Form 4a
Degree of protection (IP)IP31 – IP41
Generator back-up2 × 1,000 kVA
Verification standardIEC 61439-1, IEC 61439-2
Engineering

Project-Specific Engineering Topics

Lift starting current and protection settings

Lift drives draw a brief high current on starting. The magnetic trip threshold of the breaker is set above that transient but below the fault current.

Regenerative drives and reverse power flow

Regenerative lift drives can return energy to the network while the car descends. The metering and protection arrangement is selected to allow for that bidirectional flow.

Resonance risk from harmonics

A high density of drives increases the 5th and 7th harmonics. Detuned compensation is used so that the capacitor stages do not enter resonance with them.

Car park jet fan scenarios

Jet fans run at reduced speed in normal operation and at full speed under a smoke extraction scenario; motor outgoing ways and their protection are selected for both regimes.

FAQ

Frequently Asked Questions

Why is the lift supply circuit protected separately?

Because the lift load is characteristically different from other residential loads: it draws a brief high current on starting and its drive generates harmonics. A separately protected circuit allows the tripping curve to be set for that character and keeps a lift fault from affecting the floor lighting.

How do regenerative lift drives affect the switchboard?

Regenerative drives return the energy released as the car descends to the network. That means the direction of measurement can be bidirectional, so the power analyser and the protective devices must be selected to suit that flow.

What is the installed power at Yamanevler Avrupa Konutları?

A residential project of this scale has an installed power of approximately 4,800 kVA, with a typical transformer configuration of 3 x 1,600 kVA. The main busbar is rated at 2 x 2,500 A.

Do you have a project of a similar scale?

Send us your single-line diagram, your transformer rating or simply your load list. Our engineering team runs the short-circuit and discrimination study and defines the form of separation and busbar cross-section with you.