Thermographic Inspection of Electrical Panels: Measurement and Reporting

Thermographic panel inspection temperature difference classification

Thermographic Inspection of Electrical Panels: Measurement and Reporting

Thermographic inspection images the temperature of connections and components inside an assembly without contact, revealing problems that have not yet become failures. A loose busbar bolt or an oxidised terminal starts heating long before any breaker trips, and a thermal camera catches that early warning.

Why it is the first step in predictive maintenance

A large share of electrical failures begins with rising contact resistance. As resistance grows, more power is dissipated at that point, temperature rises, oxidation accelerates and the process feeds itself. The cycle takes weeks or even months. A survey carried out once or twice a year gives the opportunity to break it at the start.

Conditions for a valid measurement

Thermography is only meaningful under load. The general expectation is that at least 40% of rated current is flowing during the survey; below that, temperature differences disappear. Recording the load at the time of measurement is essential for comparison with later surveys. Where covers are to stay closed, infrared windows are used, which is preferable both for safety and for repeatability.

Temperature difference (ΔT) classification

What matters is not absolute temperature but the difference between similar points carrying similar load. Widely used priority bands are as follows:

Action priority by findingΔT 1–3 °C — record and keep monitoringΔT 4–15 °C — correct at the next planned outageΔT 16–40 °C — act within a short periodΔT above 40 °C — act immediatelydevpan.com
Comparison is made against similar phases or similar connection points in the same assembly.

Common findings

A hot spot alone is not a diagnosis; the pattern has to be interpreted.

PatternLikely causeAction
Spot heating at one connectionLoose or oxidised contactClean and re-torque with the panel isolated
One entire phase hotUnbalanced load distributionRedistribute loads between phases
Whole cable hotOverload or undersized conductorReview the load calculation and cable size
Device body hot, terminals normalAgeing internal componentPlan replacement of the device

Where measurement errors come from

Wrong readings usually come from surface properties. Bright copper and galvanised surfaces have low emissivity and appear colder than they really are, so applying a matt target label at measuring points is common practice. Measurement cannot be taken through glass or polycarbonate covers, because these materials do not transmit infrared. Reflections are ruled out by repeating the shot from a different angle.

What a report must contain

For a thermography report to be useful next year, it should include:

  • Date, ambient temperature and the load at the time of measurement
  • A thermal image plus a visual photograph from the same angle
  • Reference point and the ΔT value
  • The emissivity setting used and the measuring distance
  • Priority band and recommended action
  • Comparison with the previous survey

For the design-side counterpart of enclosure temperature, see thermal load and cooling.

Key takeaways: thermographic inspection

  • Why it is the first step in predictive maintenance — A large share of electrical failures begins with rising contact resistance.
  • Conditions for a valid measurement — Thermography is only meaningful under load.
  • Temperature difference (ΔT) classification — What matters is not absolute temperature but the difference between similar points carrying similar load.
  • Common findings — A hot spot alone is not a diagnosis; the pattern has to be interpreted.
  • Standard source — IEC publication catalogue: iec.ch.

Frequently asked questions

How often should thermography be carried out?

Once a year is common practice for continuously operating industrial sites. On critical processes and where loading varies widely it is increased to every six months. Taking a baseline survey in the first year after commissioning makes later comparisons meaningful.

Does thermography replace maintenance?

No. It is a diagnostic method; findings are then corrected with the equipment isolated, through torque checks, cleaning and component replacement where needed.

Can infrared windows be fitted to any panel?

They can be retrofitted to most metal enclosures, but the opening must be made without compromising enclosure integrity or the degree of protection. See IP protection ratings.

Related articles

Devpan plans measuring points and infrared window locations at the design stage of the assemblies it delivers. Share your maintenance programme and we will make your panels easier to monitor.